Scigiene’s Wireless Gen 2 AC Current Meters measure the RMS current of an alternating current (AC) system using a current transformer (CT) that wraps around the "hot" wire of a two wire (hot, common, ground (optional)) power system. The sensor reports Minimum RMS current, maximum RMS current, average RMS current, and amp hours. 20 Amp available (see related products below). Scigiene's wireless sensors are ideal for pharmaceutical, medical and other high tech applications where loss of data is unacceptable. These also have an amazing range of over 1000 ft. with 10 year battery life and can be remotely upgraded via network connections. These are truly the most advanced wireless sensors available.
Features:
* Actual range may vary depending on environment
** Battery life is determined by sensor reporting frequency and other variables
Specifications:
| 0-150 Amp
  Current Transformer | Absolute max
  CT current | 200 Amps RMS
  (A RMS) | 
| Maximum
  accurate CT current | 150 A RMS | |
| Frequency
  range | 50-100 Hz | |
| Accuracy | +/- (2% + .4
  A RMS)1 | |
| Calibrated
  accuracy with appropriate offset | +/- (1% + .2
  A RMS)1 | |
| Offset limits | -1.27 to +
  1.27 A RMS (default set to + 0.3 A RMS)2 | |
| Measurement
  resolution | ~0.1 A RMS | |
| Typical
  Deadband | ~0.3 A RMS2 | |
| Weight | 7.27 ounces
  (CT only) | |
| Lead Length | 0.9 m (3 ft) | |
| Gen 2  Wireless | Data logging | Sensor logs
  2000 to 4000 readings if gateway connection is lost (non-volatile flash,
  persists through power cycling): 10-minute Heartbeats = ~22 days - 2-hour
  Heartbeats = ~266 days | 
| Wireless
  protocol | Gen 2 Proprietary Frequency-Hopping Spread Spectrum (FHSS) | |
| Wireless transmission
  power (EIRP) | 50 mW
  (900MHz), 25 mW (868 MHz), 10 mW (433 MHz) | |
| Wireless
  range | 2,000+ ft.
  through 18+ walls with the Gen 2 XL® Gateway | |
| Security | Encrypt-RF ®
  (256-bit key exchange and AES-128 CTR) | |
| General | Battery
  voltage range | 2.0 to 3.8
  VDC | 
| Operating
  altitude (non-pressurized environments) | -15.2 to
  1,982 m (-50 to 6,500 ft)3 | |
| Storage
  altitude (non-pressurized environments) | -15.2 to
  3,048 m (-50 to 10,000 ft)3 | |
| Operating
  humidity | 5 to 85% RH
  (non-condensing) | |
| Certifications | 900 MHz
  sensors: FCC ID: ZTL-G2SC1 and IC: 9794A-G2SC1.  | |
| 1. CTs are inherently less accurate at or below 10%
  of max range. For best calibration results calibrate at a current between 30%
  and 90% of max accurate range.  2. Because of a diode inherent to the hardware, the
  sensor is incapable of reading between 0 and the deadband value. This diode
  also creates an offset. To account for this, the firmware uses offset
  compensation. 3. Operating and storage altitude without DC power supply is
  -30.48 to 9144 m (-100 to 30000 ft). | ||